Measure steam output, feedwater temperature and fuel flow over the same period at steady load.
Example
Example: 10,000 lb/h of 150 psig steam from 220 °F feedwater burning 12,500 cu ft/h of gas is 77.61% efficient — about $10 per 1,000 lb of steam.
Assumptions
Efficiency = steam × (h_steam − h_feedwater) ÷ (fuel × HHV); HHV: natural gas 1,038 BTU/cu ft, No. 2 oil 138,500 BTU/gal, propane 91,500 BTU/gal. 1 boiler hp = 33,475 BTU/h. Results are engineering and budgeting estimates — electrical work must follow the NEC and local code and be designed or checked by a licensed professional, and energy prices and incentives change.
Frequently Asked Questions
What is a good boiler efficiency?
Modern firetube steam boilers run about 80–85% (HHV); condensing hot-water boilers can exceed 90%.