SCCR Rating Calculator (Industrial Control Panel)
Determine an industrial control panel's short-circuit current rating (SCCR) from its power-circuit components and check it against the available fault current.
Determine an industrial control panel's short-circuit current rating (SCCR) from its power-circuit components and check it against the available fault current.
Results
About This Calculator
Enter the SCCR or interrupting rating of each power-circuit component (disconnect, branch protection, contactors, overloads, terminals) and the available fault current from the utility or your study.
Example
Example: with a 5 kA contactor in the power circuit the panel SCCR is 5 kA — below the 22 kA available, so it fails (margin -17 kA) unless that component gets a tested higher-rated combination.
Assumptions
Simplified UL 508A Supplement SB: the panel takes the lowest component rating unless a listed current-limiting device or tested combination raises it. NEC 409.110 requires the SCCR to be marked and to be at least the available fault current. Results are engineering and budgeting estimates — electrical work must follow the NEC and local code and be designed or checked by a licensed professional, and energy prices and incentives change.
Frequently Asked Questions
What is SCCR?
Short-circuit current rating — the maximum fault current a panel can safely withstand, required on industrial control panel nameplates.