Server & Data Center Power Cost Calculator (PUE & Cooling)

Estimate the electricity cost of running servers or a server room from the number of servers, average watts, PUE and your power price. Also gives…

Results

Enter your details and click Calculate to see your results.
About This Calculator

Use the servers' average draw, not the power supply rating; it's usually 30–60% of nameplate. PUE (power usage effectiveness) adds cooling, UPS and lighting overhead: total power = IT power × PUE.

Every watt of IT load turns into heat, so cooling must remove 3.412 BTU/h per watt.

Example

Example: 10 servers averaging 350 W in a room with PUE 1.5 at $0.14/kWh cost about $536.92 a month. They need 11,942 BTU/h of cooling.

Assumptions

Constant average load. A month is 30.44 days. Demand charges and tiered tariffs aren't included.

Frequently Asked Questions

How much does it cost to run a server 24/7?

A 300 W server uses about 219 kWh a month, which is about $30 at $0.14/kWh before cooling overhead.

What is a good PUE?

Large modern data centres run about 1.1–1.3. Small server rooms are often 1.6–2.0.