Solar String Size Calculator (Panels per String)

Find how many solar panels you can put in series per string so the cold-weather open-circuit voltage stays below the inverter's maximum and the hot-weather…

Results

Enter your details and click Calculate to see your results.
About This Calculator

Panel voltage rises in the cold, so the string's open-circuit voltage on the coldest morning must stay under the inverter's maximum DC voltage (NEC 690.7). When the panels are hot, voltage drops, so the string must still be above the MPPT minimum to keep producing.

Use the record low temperature for your site, and about 25–35 °C above the air temperature for hot cell temperature.

Example

Example: panels with Voc 49.5 V reach 54.18 V each at −10 °C, so a 600 V inverter takes up to 11 in series (3 to 11 panels per string).

Assumptions

Temperature-coefficient method (NEC 690.7(A)(2)). Shading, bifacial gain and inverter start-up voltage aren't included. Check the inverter's data sheet and local code.

Frequently Asked Questions

Why limit panels per string?

Too many in series can exceed the inverter's voltage on a cold, sunny morning and damage it.

What hot cell temperature should I use?

About 65–75 °C for roof-mounted panels in summer.

Related Calculators