Transformer Size Calculator
Size a single- or three-phase transformer — required kVA with growth margin, the next standard kVA rating, primary and secondary full-load amps and loading.
Size a single- or three-phase transformer — required kVA with growth margin, the next standard kVA rating, primary and secondary full-load amps and loading.
Results
About This Calculator
Enter the connected or demand load and voltages. Size for future growth and check harmonic (K-rated) needs for IT and LED loads.
Example
Example: a 100 kW load at 0.9 PF is 111.11 kVA; with 20% margin choose a 150 kVA 480–208Y/120 transformer (416.36 A secondary).
Assumptions
kVA = kW ÷ PF; FLA = kVA × 1,000 ÷ (√3 × V) for three-phase. Standard ratings per ANSI/IEEE C57. Results are engineering and budgeting estimates — electrical work must follow the NEC and local code and be designed or checked by a licensed professional, and energy prices and incentives change.
Frequently Asked Questions
How do I size a transformer?
Add up the load in kVA, add 20–25% for growth, and pick the next standard size.