Wire Size Calculator (Voltage Drop & Ampacity)
Find the right wire gauge for any circuit — copper or aluminum, DC, single- or three-phase, including low-voltage and solar — by ampacity and voltage…
Find the right wire gauge for any circuit — copper or aluminum, DC, single- or three-phase, including low-voltage and solar — by ampacity and voltage drop, with volts at the load.
Results
About This Calculator
Enter the load current, voltage, one-way distance and conductor. For solar PV and 12/24 V systems choose DC; keep drop under 2–3%.
Example
Example: a 40 A continuous load at 240 V, 100 ft away, needs 8 AWG copper (50 A) with a 2.55% voltage drop.
Assumptions
NEC Table 310.16 75 °C ampacities with small-conductor limits (14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A copper); resistance from NEC Chapter 9 Table 8 (aluminum ≈ 1.64× copper). Sizes listed: 14 AWG, 12 AWG, 10 AWG, 8 AWG, 6 AWG, 4 AWG, 3 AWG, 2 AWG, 1 AWG, 1/0 AWG, 2/0 AWG, 3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil, 500 kcmil. Derate for conduit fill and ambient temperature where required. Results are engineering and budgeting estimates — electrical work must follow the NEC and local code and be designed or checked by a licensed professional, and energy prices and incentives change.
Frequently Asked Questions
What size wire for 50 amps?
6 AWG copper at 75 °C for a short run; upsize for long runs to limit voltage drop.
What voltage drop is acceptable?
The NEC recommends no more than 3% on a branch circuit and 5% total.
Related Calculators