Secondary Containment Calculator
Size a secondary containment dike for oil and chemical tanks — required volume at 110% of the largest tank (or 100% plus rainfall), minimum wall…
Size a secondary containment dike for oil and chemical tanks — required volume at 110% of the largest tank (or 100% plus rainfall), minimum wall height and a check of an existing berm.
Results
About This Calculator
Enter the largest tank, the containment footprint and any other tanks that displace volume. Use the rainfall rule for uncovered outdoor containment under SPCC.
Example
Example: a 10,000 gal largest tank needs 11,000 gal of containment; inside a 40 × 30 ft dike with one other 10 ft tank the wall must be at least 15.73 in high.
Assumptions
Many fire codes require 110% of the largest tank; EPA SPCC (40 CFR 112) requires the largest container plus sufficient freeboard for precipitation. Other tanks below the wall height reduce capacity. Engineering estimates for planning — final designs must follow the applicable codes and standards and be checked by a qualified engineer, and manufacturer data overrides the typical values used here.
Frequently Asked Questions
What is the 110% rule for secondary containment?
Containment must hold 110% of the largest tank's volume — a common fire-code and industry standard.