Electrical Box Fill Calculator (Junction Box Size)
Calculate electrical box fill under NEC 314.16 — volume needed for 14 to 6 AWG conductors, devices, clamps and grounds — and whether your box…
Calculate electrical box fill under NEC 314.16 — volume needed for 14 to 6 AWG conductors, devices, clamps and grounds — and whether your box is big enough.
Results
About This Calculator
Count each insulated conductor entering the box; pigtails that start and end in the box don't count. Each device counts as two conductors, all grounds together as one, internal clamps as one.
Example
Example: two 12/2 cables (4 conductors), one receptacle, clamps and grounds need 18 cu in — an 18 cu in box works.
Assumptions
NEC 314.16(B): 14 AWG 2.0, 12 AWG 2.25, 10 AWG 2.5, 8 AWG 3.0, 6 AWG 5.0 cu in per conductor, using the largest conductor for devices, clamps and grounds. Electrical work must follow the NEC as adopted locally — check with your inspector, and hire a licensed electrician where required.
Frequently Asked Questions
How many wires can go in a single gang box?
It depends on the box volume — an 18 cu in box holds up to eight 12 AWG conductors with no device.
Related Calculators