Combustion Air Calculator (Furnace & Water Heater)
Check combustion air for gas appliances — the room volume needed for indoor air (50 cu ft per 1,000 BTU/hr) and the size of outdoor…
Check combustion air for gas appliances — the room volume needed for indoor air (50 cu ft per 1,000 BTU/hr) and the size of outdoor air openings by the NFPA 54 methods.
Results
About This Calculator
Closets and small utility rooms usually can't supply enough indoor air. Sealed-combustion (direct-vent) appliances bring in their own air and don't need these openings. Local code and the appliance manual govern.
Example
Example: a 100,000 BTU furnace plus a 40,000 BTU water heater need 7,000 cu ft of room for indoor combustion air; otherwise use two outdoor openings of 35 sq in each.
Assumptions
NFPA 54 / IFGC 304 standard method: 50 cu ft per 1,000 BTU/hr; outdoor openings 1 sq in per 4,000 BTU/hr (vertical ducts or direct), 1 per 2,000 (horizontal ducts), single opening 1 per 3,000.
Frequently Asked Questions
How much combustion air does a furnace need?
50 cu ft of room per 1,000 BTU/hr for indoor air, or outdoor air openings.