Combustion Air Calculator (Furnace & Water Heater)

Check combustion air for gas appliances — the room volume needed for indoor air (50 cu ft per 1,000 BTU/hr) and the size of outdoor…

Results

Enter your details and click Calculate to see your results.
About This Calculator

Closets and small utility rooms usually can't supply enough indoor air. Sealed-combustion (direct-vent) appliances bring in their own air and don't need these openings. Local code and the appliance manual govern.

Example

Example: a 100,000 BTU furnace plus a 40,000 BTU water heater need 7,000 cu ft of room for indoor combustion air; otherwise use two outdoor openings of 35 sq in each.

Assumptions

NFPA 54 / IFGC 304 standard method: 50 cu ft per 1,000 BTU/hr; outdoor openings 1 sq in per 4,000 BTU/hr (vertical ducts or direct), 1 per 2,000 (horizontal ducts), single opening 1 per 3,000.

Frequently Asked Questions

How much combustion air does a furnace need?

50 cu ft of room per 1,000 BTU/hr for indoor air, or outdoor air openings.

Related Calculators