Conduit Fill Calculator (NEC Chapter 9)

Check conduit fill for THHN wires in EMT, PVC Schedule 40 or 80 and rigid conduit — percent fill against the NEC limit, the maximum…

Results

Enter your details and click Calculate to see your results.
About This Calculator

Count every conductor, including grounds. More than three current-carrying conductors in a conduit also need ampacity derating (NEC 310.15(C)(1)) — fill isn't the only limit.

Example

Example: six 12 AWG THHN wires in ¾ in EMT fill 15% — within the NEC limit; up to 16 would fit.

Assumptions

NEC Chapter 9: 53% fill for one wire, 31% for two, 40% for three or more; Table 4 conduit areas and Table 5 THHN areas. Electrical work must follow the NEC as adopted locally — check with your inspector, and hire a licensed electrician where required.

Frequently Asked Questions

How many 12 gauge wires in 1/2 inch EMT?

Up to 9 THHN wires by fill.

Related Calculators