Conduit Fill Calculator (NEC Chapter 9)
Check conduit fill for THHN wires in EMT, PVC Schedule 40 or 80 and rigid conduit — percent fill against the NEC limit, the maximum…
Check conduit fill for THHN wires in EMT, PVC Schedule 40 or 80 and rigid conduit — percent fill against the NEC limit, the maximum wires that fit and the smallest conduit size that works.
Results
About This Calculator
Count every conductor, including grounds. More than three current-carrying conductors in a conduit also need ampacity derating (NEC 310.15(C)(1)) — fill isn't the only limit.
Example
Example: six 12 AWG THHN wires in ¾ in EMT fill 15% — within the NEC limit; up to 16 would fit.
Assumptions
NEC Chapter 9: 53% fill for one wire, 31% for two, 40% for three or more; Table 4 conduit areas and Table 5 THHN areas. Electrical work must follow the NEC as adopted locally — check with your inspector, and hire a licensed electrician where required.
Frequently Asked Questions
How many 12 gauge wires in 1/2 inch EMT?
Up to 9 THHN wires by fill.
Related Calculators