Pull Box Size Calculator (NEC 314.28)
Size a pull box or junction box for conductors 4 AWG and larger under NEC 314.28: minimum length for a straight pull, and distance to…
Size a pull box or junction box for conductors 4 AWG and larger under NEC 314.28: minimum length for a straight pull, and distance to the opposite wall for angle or U pulls from the raceway trade sizes.
Results
About This Calculator
Straight pull (raceways enter opposite walls): length ≥ 8 × the largest trade size. Angle or U pull (enter adjacent walls or the same wall): distance to the opposite wall ≥ 6 × the largest raceway + the sum of the other raceways entering in that row.
Calculate each direction and each row separately; the largest value sets the box dimension.
Example
Example: an angle pull with a 2" raceway plus 1½" and 1" in the same row needs 14.5" to the opposite wall.
Assumptions
Applies to conductors 4 AWG and larger (NEC 2023 314.28). For smaller conductors, use the Box Fill Calculator (NEC 314.16).
Frequently Asked Questions
What size pull box for 2" conduit straight through?
At least 16" long (8 × 2").
Does pull-box sizing apply to small wire?
No. Under 4 AWG, the volume-based box-fill rules apply instead.