Attic Ventilation Calculator (Intake & Exhaust NFA)
Calculate attic ventilation — net free area (NFA) for intake and exhaust by the 1/150 or 1/300 rule — and how many feet of ridge…
Calculate attic ventilation — net free area (NFA) for intake and exhaust by the 1/150 or 1/300 rule — and how many feet of ridge vent, box vents and soffit vents you need.
Results
About This Calculator
Find NFA on the vent's packaging (GAF, Owens Corning, Lomanco and CertainTeed all publish it). Balance intake and exhaust — at least half should be low intake — and don't mix ridge vents with gable or box vents on the same roof.
Example
Example: a 1,500 sq ft attic at 1/300 needs 720 sq in of NFA — 20 ft of ridge vent for exhaust and about 40 ft of continuous soffit vent for intake.
Assumptions
IRC R806.2: 1 sq ft NFA per 150 sq ft of attic floor, or 1/300 when 40–50% is high exhaust (or a vapor retarder is used in cold climates). Continuous soffit vent ≈ 9 sq in per ft.
Frequently Asked Questions
How many roof vents do I need?
About 1 sq ft of net free area per 300 sq ft of attic, split between intake and exhaust.