Line-to-Line Fault Current Calculator
Calculate available short-circuit current — line-to-line and three-phase bolted fault at the transformer and at the end of a cable run — using the point-to-point…
Calculate available short-circuit current — line-to-line and three-phase bolted fault at the transformer and at the end of a cable run — using the point-to-point method.
Results
About This Calculator
Enter the transformer nameplate data and the feeder to the fault point. The infinite-bus assumption (unlimited utility) gives a conservative maximum.
Example
Example: a 500 kVA, 480 V, 5.75%Z transformer can deliver 10,459 A three-phase and 9,058 A line-to-line; 100 ft of 250 kcmil drops the L-L fault to 7,370 A.
Assumptions
Point-to-point method: I = FLA ÷ %Z, L-L = 0.866 × 3φ; f = 2·L·I ÷ (C·n·E) for L-L, √3·L·I ÷ (C·n·E) for 3φ; I_end = I ÷ (1 + f). C values for copper in steel conduit, 600 V. Motor contribution is ignored. Results are engineering and budgeting estimates — electrical work must follow the NEC and local code and be designed or checked by a licensed professional, and energy prices and incentives change.
Frequently Asked Questions
Why calculate line-to-line fault current?
Line-to-line faults are lower than three-phase faults and are used to check that breakers trip quickly and for arc-flash studies.