Chilled Water Buffer Tank Sizing Calculator

Size a buffer tank for a chiller or heat pump loop from minimum capacity, minimum run time and allowed temperature swing — minus the existing…

Results

Enter your details and click Calculate to see your results.
About This Calculator

V = Q_min × t_min / (ρ·cp·ΔT); tank = V − existing loop volume.

Example

Example: 100 kW chiller, 25% minimum, 6 min run, 3 K → 216.675 L tank.

Assumptions

Water (4.186 kJ/kg·K); follow the manufacturer's minimum-volume rule if larger.

Frequently Asked Questions

Why a buffer tank?

It prevents short-cycling when the load is smaller than the smallest capacity step.

Related Calculators