Chilled Water Buffer Tank Sizing Calculator
Size a buffer tank for a chiller or heat pump loop from minimum capacity, minimum run time and allowed temperature swing — minus the existing…
Size a buffer tank for a chiller or heat pump loop from minimum capacity, minimum run time and allowed temperature swing — minus the existing system volume.
Results
Enter your details and click Calculate to see your results.
About This Calculator
V = Q_min × t_min / (ρ·cp·ΔT); tank = V − existing loop volume.
Example
Example: 100 kW chiller, 25% minimum, 6 min run, 3 K → 216.675 L tank.
Assumptions
Water (4.186 kJ/kg·K); follow the manufacturer's minimum-volume rule if larger.
Frequently Asked Questions
Why a buffer tank?
It prevents short-cycling when the load is smaller than the smallest capacity step.