4-20 mA Calculator
Scale a 4–20 mA signal to engineering units and back — value from current, current from value, percent of span, 1–5 V across 250 Ω…
Scale a 4–20 mA signal to engineering units and back — value from current, current from value, percent of span, 1–5 V across 250 Ω and NAMUR NE 43 fault check.
Results
About This Calculator
Enter the transmitter's calibrated range, then a current to convert to a value or a value to convert to the expected current.
Example
Example: 12 mA on a 0–150 psi transmitter reads 75 psi — 50% of span (3 V across a 250 Ω resistor).
Assumptions
Linear scaling: value = low + (mA − 4) ÷ 16 × span. NAMUR NE 43: below 3.8 mA or above 20.5 mA indicates a fault. Engineering estimates for planning — final designs must follow the applicable codes and standards and be checked by a qualified engineer, and manufacturer data overrides the typical values used here.
Frequently Asked Questions
Why is 4–20 mA used instead of 0–20?
A live zero at 4 mA lets you tell a 0% reading apart from a broken wire (0 mA).
Related Calculators