Buck-Boost Transformer Calculator (Sizing kVA)
Size a buck-boost transformer to raise or lower a supply voltage, such as 208 V to 230 V or 480 V to 460 V. Gives…
Size a buck-boost transformer to raise or lower a supply voltage, such as 208 V to 230 V or 480 V to 460 V. Gives the voltage change, the buck-boost kVA needed and the standard unit size, for single-phase or three-phase loads.
Results
About This Calculator
A buck-boost transformer is wired as an autotransformer. Its low-voltage secondary adds to the supply (boost) or subtracts from it (buck). It only handles the voltage difference, so kVA = load amps × voltage change ÷ 1,000. That is a small fraction of the load.
Pick a standard unit at or above the result, with secondaries of 12/24 V, 16/32 V or 24/48 V.
Example
Example: boosting 208 V to 230 V for a 30 A load needs only 0.66 kVA of buck-boost transformer (0.75 kVA × 1), because it carries just the 10.6% voltage difference.
Assumptions
Three-phase uses three units in a wye arrangement (open delta with two units also works for many loads). Check the manufacturer's connection diagram. Buck-boost units don't provide isolation.
Frequently Asked Questions
Can I run a 230 V appliance on 208 V?
Many motors and heaters run poorly or slowly on 208 V. A small buck-boost transformer raises it to about 230 V.