Earth Fault Loop Impedance (Zs) Calculator
Calculate earth fault loop impedance Zs from Ze and cable R1 + R2, the prospective fault current, and check it against the maximum Zs for…
Calculate earth fault loop impedance Zs from Ze and cable R1 + R2, the prospective fault current, and check it against the maximum Zs for a B, C or D type MCB.
Results
About This Calculator
Zs = Ze + (R1 + R2)·L·temperature factor; max Zs = 0.95·U₀/Ia with Ia = 5, 10 or 20 × In (BS 7671 Cmin = 0.95).
Example
Example: Ze 0.35 Ω, 25 m of 2.5/1.5 mm² → Zs = 0.9353 Ω vs max 1.36563 Ω.
Assumptions
2.5/1.5 mm² copper twin & earth = 19.51 mΩ/m at 20 °C. Verify against BS 7671 tables.
Frequently Asked Questions
Why multiply by 1.2?
Conductors run hotter under load, raising resistance.
Related Calculators