Fault Current Calculator (Available Short-Circuit Current)

Estimate the available short-circuit (fault) current at a transformer's secondary and at the end of a copper feeder, using the point-to-point method. Use it to…

Results

Enter your details and click Calculate to see your results.
About This Calculator

At the transformer, Isc = FLA × 100 ÷ %Z. The %Z is reduced by 10% to cover the manufacturing tolerance, as Eaton Bussmann recommends. The feeder then limits the current: f = √3 × L × I ÷ (C × n × V) for three-phase, and Isc at the end = Isc × 1/(1 + f).

Every breaker, fuse and panel must have an interrupting rating (AIC/SCCR) above the fault current where it's installed.

Example

Example: a 500 kVA, 480 V, 5%Z transformer can deliver about 13365 A at its terminals. After 100 ft of 4/0 copper that falls to about 10127 A.

Assumptions

Infinite utility source (worst case), no motor contribution (add about 4 × motor FLA), and Bussmann C values for copper in steel conduit at 600 V. Use a full study for arc-flash work.

Frequently Asked Questions

What is the fault current of a 1,000 kVA transformer?

About 26,700 A at 480 V with 5% impedance (using the 10% tolerance).

Why does a longer cable reduce fault current?

Its impedance adds to the transformer's, limiting how much current can flow into a short.