Fault Current Calculator (Available Short-Circuit Current)
Estimate the available short-circuit (fault) current at a transformer's secondary and at the end of a copper feeder, using the point-to-point method. Use it to…
Estimate the available short-circuit (fault) current at a transformer's secondary and at the end of a copper feeder, using the point-to-point method. Use it to check equipment interrupting and SCCR ratings.
Results
About This Calculator
At the transformer, Isc = FLA × 100 ÷ %Z. The %Z is reduced by 10% to cover the manufacturing tolerance, as Eaton Bussmann recommends. The feeder then limits the current: f = √3 × L × I ÷ (C × n × V) for three-phase, and Isc at the end = Isc × 1/(1 + f).
Every breaker, fuse and panel must have an interrupting rating (AIC/SCCR) above the fault current where it's installed.
Example
Example: a 500 kVA, 480 V, 5%Z transformer can deliver about 13365 A at its terminals. After 100 ft of 4/0 copper that falls to about 10127 A.
Assumptions
Infinite utility source (worst case), no motor contribution (add about 4 × motor FLA), and Bussmann C values for copper in steel conduit at 600 V. Use a full study for arc-flash work.
Frequently Asked Questions
What is the fault current of a 1,000 kVA transformer?
About 26,700 A at 480 V with 5% impedance (using the 10% tolerance).
Why does a longer cable reduce fault current?
Its impedance adds to the transformer's, limiting how much current can flow into a short.