Fuse Size Calculator (Load, Motor & Transformer Primary)

Find the right fuse rating for a continuous load, a motor branch circuit (dual-element or non-time-delay) or a transformer primary, using NEC percentages and standard…

Results

Enter your details and click Calculate to see your results.
About This Calculator

Continuous loads (3 hours or more) need protection at 125% of the load. Motors need room for starting current: NEC 430.52 allows dual-element time-delay fuses up to 175% of FLA, or non-time-delay fuses up to 300%, rounded up to the next standard size.

Transformer primaries alone (NEC 450.3(B)): 125% for 9 A and up, 167% for 2–9 A and 300% below 2 A.

Example

Example: a motor with a 28 A FLA on dual-element fuses can use 49 A, so the next standard size is 50 A.

Assumptions

Standard ratings from NEC 240.6(A). Use the motor FLA from NEC tables 430.248/430.250, not the nameplate, for motor circuits. Always follow the equipment's marked maximum fuse.

Frequently Asked Questions

What size fuse for a 20 A continuous load?

25 A (125%), with wire rated for it.

Why can a motor fuse be bigger than the wire?

Motor overload relays protect the wire from overload; the fuse only handles short circuits, so it must ride through starting current.