Fuse Size Calculator (Load, Motor & Transformer Primary)
Find the right fuse rating for a continuous load, a motor branch circuit (dual-element or non-time-delay) or a transformer primary, using NEC percentages and standard…
Find the right fuse rating for a continuous load, a motor branch circuit (dual-element or non-time-delay) or a transformer primary, using NEC percentages and standard fuse sizes.
Results
About This Calculator
Continuous loads (3 hours or more) need protection at 125% of the load. Motors need room for starting current: NEC 430.52 allows dual-element time-delay fuses up to 175% of FLA, or non-time-delay fuses up to 300%, rounded up to the next standard size.
Transformer primaries alone (NEC 450.3(B)): 125% for 9 A and up, 167% for 2–9 A and 300% below 2 A.
Example
Example: a motor with a 28 A FLA on dual-element fuses can use 49 A, so the next standard size is 50 A.
Assumptions
Standard ratings from NEC 240.6(A). Use the motor FLA from NEC tables 430.248/430.250, not the nameplate, for motor circuits. Always follow the equipment's marked maximum fuse.
Frequently Asked Questions
What size fuse for a 20 A continuous load?
25 A (125%), with wire rated for it.
Why can a motor fuse be bigger than the wire?
Motor overload relays protect the wire from overload; the fuse only handles short circuits, so it must ride through starting current.