Inrush Current Calculator (Transformer, Motor & Power Supply)
Estimate inrush current when a transformer is energised, a motor starts (from its NEC code letter) or a capacitive power supply is switched on with…
Estimate inrush current when a transformer is energised, a motor starts (from its NEC code letter) or a capacitive power supply is switched on with an NTC limiter. Shows the peak, full-load current and multiple.
Results
About This Calculator
Transformers draw a short magnetising surge, typically 8–12 × full-load current for about 0.1 s. Motors draw locked-rotor current until they reach speed. The NEC code letter on the nameplate gives the locked-rotor kVA per horsepower.
Switch-mode power supplies charge their bulk capacitor at switch-on; an NTC thermistor limits the peak to about √2 × V ÷ R.
Example
Example: energising a 75 kVA three-phase 480 V transformer draws about 1082.5 A, which is 12 × its 90.211 A full-load current.
Assumptions
Worst-case estimates for choosing time-delay fuses and breakers. Real transformer inrush depends on the switching point on the waveform and on residual flux.
Frequently Asked Questions
How much inrush does a motor draw?
Typically 6–8 × full-load current for a code G–H motor across the line. Soft starters and VFDs reduce it.
Why do breakers trip when a transformer is switched on?
Magnetising inrush can reach 12 × FLA. Use time-delay protection or a higher instantaneous setting.