Electric Motor Full Load Current & Torque Calculator

Calculate an electric motor's full-load current, input power, torque and approximate starting current from HP or kW, voltage, efficiency and power factor.

Results

Enter your details and click Calculate to see your results.
About This Calculator

I = P/(√3·V·η·PF) three-phase or P/(V·η·PF) single-phase; torque = P/(2π·rpm/60); 1 hp = 0.7457 kW.

Example

Example: 10 hp, 400 V three-phase → 14.0696 A full-load.

Assumptions

For NEC conductor sizing use Table 430.250 values rather than nameplate calculations.

Frequently Asked Questions

Why is starting current so high?

At standstill there's no back-EMF — direct-on-line starts draw 5–8 × FLA.